AC/DC Hall Effect Sensor – HCT-0016-100 by Magnelab

$55.00

Auswahl zurücksetzen

All HCT devices require Active Power

Artikelnummer: k.A.
Product Description

The HCT-0016-100 is a AC/DC Hall Effect Sensor that takes 100A and outputs 4V and a 16 mm opening.

This AC/DC Hall effect sensor can be used to measure both DC amperage as well as AC amperage signals up to 100A. This Hall effect sensor can be used for a variety of purposes. The output type (AC or DC) reflects the type of the input amperage. The HCT-0016 is very compact and lightweight. The HCT-0016 has an offset voltage less than +/-30 mV. It is +/-1% linear.

Temperature has a ± 0.1% /°C effect on this open loop AC/DC Hall effect sensor (open loop hall effect device). The HCT-0016 uses accurate laminating core split technology and is designed for strong durability while providing accuracy in low current situations. The HCT-0016 is a compact one-touch split structure, allowing easy installation. It is 1% accurate at the rated current and passes IEC61010-1, UL61010-1, and EN61010-1.

The HCT-0016’s insulation can withstand an AC voltage up to 1500V for 1 minute.  It typically has a 3 μ sec response time at full scale current.

When searching for compatible power meters, look for meters on our website that accept a Vdc input. These meters will show the following symbol as the input:

DC Voltage

To power the HCT-0016 you will need a +/-15Vdc power supply (+/-5%).

You can view all of our current sensors here.

Zusätzliche Information

Gewicht0.3 lbs
Größe1.2 x 2 x 3 in
Amp Rating

10, 100, 20, 25, 5, 50