Questions? Contact Us Now +1 (303) 772-6100

Automation &
Monitoring Solutions.

G4BM480V12AFTL20 by Tele Haase

Manufacturer: Tele Haase
SKU: G4BM480V12AFTL20
$601.28
Availability: Available in 1 Week
Non-Stock Lead Time: 1 Week
Minimum Order Quantity is 1
Products specifications
Attribute nameAttribute value
SeriesGamma
Phase1P2W, 3P3W
ContactDPDT, 2CO
Input0~277 Vac 3Φ, 0~480 Vac 1Φ, 0~480 Vac 3Φ
Range0.5kW, 1kW, 2kW, 4kW
Overload Capacity Voltage1Φ 550 Vac, 3φ 318 Vac, 3φ 550 Vac
Supply Voltage12~500 Vac

Description

The TELE G4BM480V12AFTL20 provides True power monitoring in 1- and 3-phase mains with adjustable thresholds (P1 and P2), the timing for start-up suppression time and tripping delay separately adjustable, selectable fault latch, temperature monitoring of the motor winding with max. 6 PTC, reset-key and more

  • Multifunction
  • Temperature monitoring of the motor winding
  • Reset-key
  • Fault latch
  • Recognition of disconnected load
  • Suitable for VFI (10 to 100Hz)
  • Supply voltage selectable via power modules
  • DPDT / 2 change over contacts
  • Width 45mm
  • Industrial design
  • Functions
    • 2MIN : Minimum monitoring
    • 2MIN+I=0 ON : Minimum monitoring and recognition of disconnected consumers (relay ON if I=0)
    • 2MIN+I=0 Inv. : Minimum monitoring and recognition of disconnected consumers (relay OFF if I=0 Inv.)
    • 2MAX : Maximum monitoring
    • 2MAX+I=0 ON : Maximum monitoring and recognition of disconnected consumers (relay OFF if I=0)
    • 2MAX+I=0 Inv. : Maximum monitoring and recognition of disconnected consumers (relay OFF if I=0 Inv.)
    • WIN : Monitoring the window between MIN and MAX
    • WIN+I=0 ON : Monitoring the window between MIN and MAX and recognition of disconnected consumers (relay ON if I=0)
    • WIN+I=0 Inv. : Monitoring the window between MIN and MAX and recognition of disconnected consumers (relay OFF if I=0 Inv.)
    • MIN/MAX : Minimum- and maximum monitoring
    • MIN/MAX+I=0 ON : Minimum- and maximum monitoring and recognition of disconnected consumers (relay ON if I=0)
    • MIN/MAX+I=0 Inv. : Minimum- and maximum monitoring and recognition of disconnected consumers relay OFF if I=0 Inv.)