Aim DynamicsAutomation & Monitoring Solutions.
Automation &
Monitoring Solutions.

G2PU690VS20 by Tele Haase

$180.33
Stock: 5 units
Non-Stock Lead Time: 1 Week
SKU: G2PU690VS20

Attributes

Categories Monitoring Relays
Manufacturer/Brand Tele Haase
Series Gamma
Mfr Part No 2390507
Switching Capacity 75VA (2.5A@30Vdc), 150VA (5A@30Vdc), 1250VA (5A@250Vac), 1250VA
Measuring Variable Voltage
Measuring Input 208-690 Vac
Tripping Delay 0.1~10s
Phase Config 3P3W
Number of Functions 3.00
Functionality Phase Failure, Phase Sequence, Under Voltage
Has LED Yes
Contact DPDT, 2CO
Power Type AC
Supply Voltage 208-690 Vac
Switching Voltage 250 Vac
Operating Temperature -25° to 55°C, -13° to 131°F
Safety Approvals cULus, EAC
Safety Standards CE
Depth (in) 4.06
Height (in) 3.54
Width (in) 0.89
Weight (lbs) 0.32
Depth (mm) 103.00
Height (mm) 90.00
Width (mm) 22.50
Weight (kg) 0.100
Origin Austria
Non-Stock Lead Time 1 Week

Description

The TELE G2PU690VS20 is a 3-Phase voltage monitoring device that measures between 208V and 690V providing Under voltage monitoring (UNDER, UNDER+SEQ), Phase sequence monitoring (SEQ) and Phase failure monitoring with a DPDT / 2CO (Double Pole Double Throw) contact

  • This is a direct replacement for NEA462544, Phase Relay PF3 200-600V, Phase Relay for Schindler 9300, SWE
  • Functions
    • Undervoltage Monitoring
    • Phase Sequence Monitoring
    • Phase Failure Monitoring
  • Supply voltage = measuring voltage
  • DPDT / 2 change-over contacts
  • Width 22.5mm
  • Industrial design
  • Indicators
    • Green LED U ON: indication of supply voltage
    • Red LED MIN ON: indication of failure - undervoltage
    • Red LED MIN flashes: indication of tripping delay
    • Red LED SEQ ON: indication of failure - phase sequence
    • Yellow LED ON/OFF: indication of relay output
  • Input circuit
    • Supply voltage: 3~ 208V - 690V
    • Tolerance: 3~ 177V - 794V
    • Rated surge voltage: 6kV
  • Output circuit
    • Rated voltage: 250 Vac
    • Max. switching voltage: 400 Vac
    • Rated surge voltage: 6kV
  • Switching capacity
    • 1250VA (5A / 250 Vac) @ +55°C
    • 150VA (5A / 30 Vdc) @ +55°C
    • 75VA (2.5A / 30 Vdc) @ +70°C