Aim DynamicsAutomation & Monitoring Solutions.
Automation &
Monitoring Solutions.

G4BM480V12ADTL20 24-240V AC/DC by Tele Haase

$628.03
Stock: 7 units
Non-Stock Lead Time: 1 week
Power Supply
SKU: G4BM480V12ADTL20 24-240V AC/DC

Attributes

Categories Load Monitors
Mfr Part No 2394706
Manufacturer/Brand Tele Haase
Series Gamma
Phase Config 1P2W, 3P3W
Contact DPDT, 2CO
Measuring Variable True Power
Measuring Input 48~277 Vac 3Φ, 48~480 Vac 1Φ, 48~480 Vac 3Φ
Tripping Delay 0.1~50s
Start-Up Suppression Time 0~100s
Measuring Range 2.5kW - 10kW
Overload Capacity Voltage 1Φ 550 Vac, 3φ 550 Vac
Width (mm) 45.00
Safety Approvals cULus, EAC
Safety Standards CE
Functionality 2MAX, 2MAX+I=0 ON, 2MIN, 2MIN+I=0 ON, MAX/MIN, MAX/MIN+I=0 ON, OVER, OVER+I=0 ON, UNDER, UNDER+I=0 ON, WIN, WIN+I=0 ON
Measuring Input Current 0.15 - 6A, 0.3 - 12A
Overload Capacity Current 12A permanent
Switching Capacity 750VA (3A@250Vac)
Supply Voltage 24-240 Vdc, 24-240 Vac
Weight (lbs) 0.73
Origin Austria
Non-Stock Lead Time 1 week

Description

The TELE G4BM480V12ADTL20 24-240V AC/DC provides True power monitoring for 1- or 3-phase loads with adjustable switching thresholds, adjustable start-up suppression time, separately adjustable tripping delay, selectable fault latch and temperature monitoring of the motor winding

  • Digital setting
  • Multifunction
  • Temperature monitoring of the motor winding
  • Fault latch
  • Recognition of disconnected load
  • Suitable for VFI (10 to 100Hz)
  • Supply voltage selectable via power modules
  • DPDT / 2 change over contacts
  • Width 45mm
  • Industrial design
  • Functions
      OVER : Overload monitoring
    • OVER+I=0 : ON Overlaod monitoring and recognition of disconnected load (relay ON or OFF)
    • UNDER : Underload monitoring
    • UNDER+I=0 : ON Underlaod monitoring and recognition of disconnected load (relay ON or OFF)
    • 2MIN : Minimum monitoring
    • 2MIN+I=0 : ON Minimum monitoring and recognition of disconnected load (relay ON or OFF)
    • 2MAX : Maximum monitoring
    • 2MAX+I=0 : ON Maximum monitoring and recognition of disconnected load (relay ON or OFF)
    • WIN : Monitoring the window between MIN and MAX
    • WIN+I=0 : ON Monitoring the window between MIN and MAX and recognition of disconnected load (relay ON or OFF)
    • MAX/MIN : Maximum- and minimum monitoring
    • MAX/MIN+I=0 : ON Maximum- and minimum monitoring and recognition of disconnected load (relay ON or OFF)

Related products

Use this form to report an issue you found on this page. If you provide your name & email address, we will notify you when the issue has been resolved.

Be as specific as possible.

    Report an issue