V4LM4S30 24-240V AC/DC by Tele Haase

$207.50
QuantityDiscounted Price
Stock: 0 units
Non-Stock Lead Time: 1 Week
Probe
SKU: V4LM4S30 24-240V AC/DC

Attributes

Categories Monitoring Relays, Motor Controls
Mfr Part No 2104500
Series Veo
Manufacturer/Brand Tele Haase
Functionality Liquid Level Monitor, Overflow Control, Pump Controller, Pump Down, Pump Up
Contact 3NO, 3PNO
Measuring Variable Liquid Level
Voltage 24-240 Vdc, 24-240 Vac
Measuring Input High: 10kΩ-500kΩ, Low: 250Ω-12.5kΩ
Tripping Delay 0s
Start-Up Suppression Time 0s
Safety Approvals EAC, UL Listed
Width (mm) 45.0
Safety Standards CE
Switching Capacity 5A @ 250 Vac, 1250 VA
Supply Voltage 24-240 Vdc, 24-240 Vac
Weight (lbs) 0.322
Non-Stock Lead Time 1 Week

Description

The V4LM4S30 24-240V AC/DC is a Multifunction Liquid Level Monitor for conductive liquids with 4 probe inputs and 3 normally open contacts with common root.

  • Features
    • Level monitoring in conductive liquids
    • 4 probe inputs for level monitoring
    • Multifunction
    • Adjustable sensor voltage
    • Supply voltage 24-240V AC/DC
    • Protective separation of measuring circuit
    • 3 normally open contacts with common root
    Control elements
    • Sensitivity
    • Sensor voltage / Measuring range
    • Function
    • Delay / Operating mode
    Status indication
    • LED U/t: Supply voltage / time lapse
    • LED R1: Relay status Rel1
    • LED R2: Relay status Rel2
    • LED R3: Relay status Rel3
    • LED PP1: Pump performance 1
    • LED PP2: Pump performance 2
    Technical Data
    • Supply voltage: 24...240 Vac/Vdc
    • Backup power time: < 30 ms
    • Recovery time: < 500 ms
    • Drop-out voltage: ≥ 6 V
    • Measuring method: Resistance measurement E1-E0, E2-E0, E3-E0, E4-E0
    • Monitoring function: Level monitoring of conductive liquids with adjustable delay (measuring filter)
    Range of Functions
    • 2uA = Pump up; Min- / Max-Alarm (1 container, 4 probes)
    • 2dA = Pump down; Min- / Max-Alarm (1 container, 4 probes)
    • 3b- = Pump up and down; Min-Alarm (1 container, 3 (4) probes)
    • 3b+ = Pump up and down; Max-Alarm (1 container, 3 (4) probes)
    • 2u2 = Pump up (2 independent containers, 2 probes each)
    • 2d2 = Pump down (2 independent containers, 2 probes each)
    • 2uc = Pump up with pump change (1 container, 2 probes)
    • 2dc = Pump down with pump change (1 container, 2 probes)
    • 3w- = Well control; Min-Alarm (2 containers, 3 probes)
    • 4ce = Level code (up to 4 containers, 4 probes)