Questions? Contact Us Now +1 (303) 772-6100

Automation &
Monitoring Solutions.

V4LM4S30 24-240V AC/DC by Tele Haase

Manufacturer: Tele Haase
SKU: V4LM4S30 24-240V AC/DC
$267.17
Availability: Available in 1 Week
Non-Stock Lead Time: 1 Week
Minimum Order Quantity is 1
Products specifications
Attribute nameAttribute value
SeriesVeo
Contact3NO, 3PST-NO
Phase1P2W
Input10kΩ~500kΩ High, 250Ω~12.5kΩ Low
Supply Voltage24~240 Vac, 24~240 Vdc

Description

The V4LM4S30 24-240V AC/DC is a Multifunction Liquid Level Monitor for conductive liquids with 4 probe inputs and 3 normally open contacts with common root

Features

  • Level monitoring in conductive liquids
  • 4 probe inputs for level monitoring
  • Multifunction
  • Adjustable sensor voltage
  • Protective separation of measuring circuit
  • 3 normally open contacts with common root

Control elements

  • Sensitivity
  • Sensor voltage / Measuring range
  • Function
  • Delay / Operating mode

Status indication

  • LED U/t: Supply voltage / time lapse
  • LED R1: Relay status Rel1
  • LED R2: Relay status Rel2
  • LED R3: Relay status Rel3
  • LED PP1: Pump performance 1
  • LED PP2: Pump performance 2

Technical Data

  • Supply Voltage
    • 24 to 240 Vac
    • 24 to 240 Vdc
  • Backup power time: < 30 ms
  • Recovery time: < 500 ms
  • Drop-out voltage: ≥ 6 V
  • Measuring method: Resistance measurements
    • E1-E0
    • E2-E0
    • E3-E0
    • E4-E0
  • Monitoring function: Level monitoring of conductive liquids with adjustable delay (measuring filter)

Range of Functions

  • 2uA = Pump up; Min- / Max-Alarm (1 container, 4 probes)
  • 2dA = Pump down; Min- / Max-Alarm (1 container, 4 probes)
  • 3b- = Pump up and down; Min-Alarm (1 container, 3 (4) probes)
  • 3b+ = Pump up and down; Max-Alarm (1 container, 3 (4) probes)
  • 2u2 = Pump up (2 independent containers, 2 probes each)
  • 2d2 = Pump down (2 independent containers, 2 probes each)
  • 2uc = Pump up with pump change (1 container, 2 probes)
  • 2dc = Pump down with pump change (1 container, 2 probes)
  • 3w- = Well control; Min-Alarm (2 containers, 3 probes)
  • 4ce = Level code (up to 4 containers, 4 probes)