Questions? Contact Us Now +1 (303) 772-6100

Automation &
Monitoring Solutions.

ACTL-0750-150 Opt C0.6 150A Input 333mV Output Split-Core Current Transducer by Continental Control Systems

SKU: ACTL-0750-150 Opt C0.6
$72.68
Availability: 65 in stock
Non-Stock Lead Time: 2 Weeks
Minimum Order Quantity is 1
Products specifications
Attribute nameAttribute value
Input Rating (A)150
Output0.333 Vac
Shape/StyleSplit-Core
Error %0.5
Opening (greatest dim.)0.8 in (20 mm)
# of Inputs1
SeriesACTL

Description

The patented Accu-CT split-core current transformer technology delivers exceptional linearity and low-end accuracy

  • Developed specifically for solar inverter, variable speed motor drive, and other applications where there are large variations in current
  • The 100:1 turn down ratio of Accu-CTs is ten times better than industry standard CTs
  • The unique one-handed opening and closing mechanism makes installation a snap
  • Square 0.75 in. Window Opening
  • Safe: built-in burden resistor provides 0.333 Vac voltage output at the rated full scale current—no shorting blocks needed
  • UL 2808 Listed meets 2017 NEC code requirements for field installed current transformers
  • IEEE C57.13 and IEC 60044-1 accuracy: over full temperature range and down to below 1% of rated current
  • Exceptionally low phase angle error: essential for accurate power and energy measurements
  • Glove-friendly: easy to open and install with one hand while wearing safety gloves
  • 333mV Output
  • REVENUE GRADE ACCURACY
    • With Option C0.6, the Accu-CT is calibrated and verified to meet IEEE/ANSI C57.13-2008 class 0.6 accuracy and IEC 60044-1 class 0.5 S accuracy and each CT is shipped with a certificate of calibration
    • When used on 50 Hz services, Option C0.6 must be ordered with Option 50Hz
    • Accuracy: ±0.50% from 1% to 120% of rated primary current
    • Phase angle: ±0.25 degrees (15 minutes) from 1% to 120% of rated current; ±0.50 degrees (30 minutes) below 0°C from 1% to 10% of rated current
    • IEEE C57.13 accuracy: class 0.6 from 1% to 120% of rated current
    • IEC 60044-1 accuracy: class 0.5 and 0.5 S from 1% to 120% of rated current
    • Note: The ACTL-0750-250 Opt C0.6 model specifications are valid only to 40°C
Part NoOpening (mm) Input Rating (A)Output
ACTL-0750-020 Opt C0.620 mm200.333 V
ACTL-0750-050 Opt C0.620 mm500.333 V
ACTL-0750-100 Opt C0.620 mm1000.333 V
ACTL-0750-150 Opt C0.620 mm1500.333 V
ACTL-0750-200 Opt C0.620 mm2000.333 V
ACTL-0750-250 Opt C0.620 mm2500.333 V
ACTL-1250-250 Opt C0.646.5 mm2500.333 V
ACTL-1250-400 Opt C0.646.5 mm4000.333 V
ACTL-1250-600 Opt C0.646.5 mm6000.333 V

Cross References:
Optosolutions
OPTOEMU-ACT-0750-050
OPTOEMU-ACT-0750-100
OPTOEMU-ACT-0750-150
OPTOEMU-ACT-0750-250
Schneider
METSECTLV2010U
METSECTLV2020U