Attribute name | Attribute value |
---|
Input Rating (A) | 20, 50, 100, 150, 200, 250, 50000 |
Input | 400 Vac L-N, 690 Vac L-L |
CT Input | 333mV, Rogowski Coil |
Shape/Style | Rogowski Coil, Solid-Core, Split-Core |
Functionality | Current, Energy, Frequency, Phase, Power, Time-of-Use |
Error % | 0.5 |
Communication | BACnet/IP, BACnet MS/TP, Modbus RTU, Modbus TCP/IP, RS485 |
# of Inputs | 4 |
Phase | 1P2W, 1P3W, 3P3W, 3P4W |
Datalogging | Yes |
Supply Voltage | 100~415 Vac, 100~300 Vdc |
Enclosure | Indoor Steel Panel, Indoor / Outdoor Waterproof Polycarbonate Panel |
Series | AcuPanel, Acuvim |
Description
The Acuvim L is a cost-effective, multifunction power and energy meter that offers value and high-performance for a wide range of standard metering projects
- mV: 333mV and Rogowski Coil (Input Field Selectable)
- Designed for easy integration into panel or device monitoring applications, the plug-in expansion modules allow communication across Modbus-RTU or Profibus networks and the tough NEMA rated design ensures years of dependable use in harsh environments
- In addition, the Acuvim L features revenue grade accuracy and can be configured as either a panel-mount device, as a DIN rail mount transducer, or installed in a pre-configured, pre-wired AcuPanel for extreme protection in even the toughest application environments
- Features
- EL Revenue Grade: ANSI C12.20 class 0.2 & IEC 62053-22 class 0.2s
- CL Revenue Grade: ANSI C12.20 class 0.5 & IEC 62053-22 class 0.5s
- 4th CT input – Measure neutral current
- Dual Ethernet Ports with both RSTP bridge daisychain mode and separately configurable network
- Data Logging available in 16MB, and 8GB with WEB2 module
- Designed with industry - leading cybersecurity
- Available compatibility with multiple CT output options including 5A, RCT (Rogowski), or 333mV
- Modbus-RTU & BACnet MS/TP ready
- Optional modules add support for multiple industrial protocols & interfaces such as Modbus-TCP/IP, BACnet-IP, IEC 61850, Wi-Fi, & EtherNet/IP
- AcuPanel 9104/9104X Pre-Wired Power & Energy Panel Meter
- The AcuPanel 9104/9104X is a convenient, pre-configured meter enclosure that delivers streamlined meter deployment in OEM or retrofit projects
- It is ideal for when installation inside an electrical distribution panel is unavailable, in harsh environments to safeguard instrumentation against
the elements, or to limit the time and complexity of installation - Each AcuPanel undergoes rigorous quality testing to ensure years of dependable service
- Features
- The AcuPanel 9104/9104X is a convenient, pre-configured meter enclosure that delivers streamlined meter deployment in OEM or retrofit
projects - It is ideal for when installation inside an electrical distribution panel is unavailable, in harsh environments to safeguard instrumentation against
the elements, or to limit the time and complexity of installation - Each AcuPanel undergoes rigorous quality testing to ensure years of dependable service
- Choose from a NEMA 3 rated industrial steel enclosure or NEMA 4X rated polycarbonate enclosure suitable for both indoor and outdoor use
- The lockable, plug-and-play housing provides protection against unwanted tampering and the elements
- Clean, factory pre-wiring for fast, reliable installation
- All necessary fuses, shorting blocks, & terminal blocks are pre-installed and labeled
- Self-powered panel does not require a separate power supply
- Wires can be run through pluggable, pre-cut holes
- Simple grounding is included inside each enclosure
- No control transformer needed
- Compatible with the Acuvim II Series, Acuvim IIBN, Acuvim L, and EV300 meters
Input Option: | Opening | Input Amps |
ATR-120MV-04 | 4" Diameter Thin Rogowski Coil | 500 mA – 100 kA |
ATR-120MV-07 | 7" Diameter Thin Rogowski Coil | 500 mA – 100 kA |
ATR-120MV-11 | 11" Diameter Thin Rogowski Coil | 500 mA – 100 kA |
ACTL-0750-020 | 0.78 in (20 mm) | 20 |
ACTL-0750-050 | 0.78 in (20 mm) | 50 |
ACTL-0750-100 | 0.78 in (20 mm) | 100 |
ACTL-0750-150 | 0.78 in (20 mm) | 150 |
ACTL-0750-200 | 0.78 in (20 mm) | 200 |
ACTL-0750-250 | 0.78 in (20 mm) | 250 |
Communication Modules (Optional) | |
Part No | Description |
AXM-PROFI | Profibus-DP |
AXM-RS485 | Additional RS485 |
AXM-WEB2 | Dual Port Ethernet Communication Module + 8GB data logging + Wi-Fi |
AXM-WEB2-D | Dual Port Ethernet Communication Module + 8GB data logging |
AXM-WEB2-FOLC | Ethernet + Fiber LC Communication Module + 8GB data logging + Wi-Fi |
AXM-WEB-PUSH | Ethernet Communication Module + 4GB data logging |
I/O Modules (Optional) | |
Part No | Description |
AXM-IO1 | 6DI, 1 Power Supply for DI, 2RO |
AXM-IO2 | 4DI, 2DO, 2AO |
AXM-IO3 | 4DI, 2RO, 2AI |
Mounting Accessory (Optional) | |
Part No | Description |
AXM-DIN | DIN Rail Mounting Accessory |