Products specifications
Attribute nameAttribute value
Pressure UnitInches of Water Column
Pressure Range0.25
DirectionBi-directional, Uni-directional
Supply Voltage12~36 Vdc, 16~36 Vdc, 21~36 Vdc, 24 Vac
Output4~20 mA, 0~5 Vdc, 0~10 Vdc
Error %0.25, 0.5
SeriesMLP2

Description

The MLP2 Series Low Differential Pressure transmitters are designed for use in OEM or high density panel mounting applications

  • Key installation features include an integral 35 mm DIN rail mounting foot, vertically orientated wiring and pressure connections, and a pushbutton zero function conveniently located on the front cover
  • The MLP2 offers two options for DIN Rail mounting; rear and side mount
  • The rear DIN rail mount is integrated into the enclosure
  • The side mount adapter is included with the package, and can easily be attached
  • The side mount offers a much thinner profile for higher density panels
  • The MLP2 incorporates a high accuracy, piezoresistive, silicon sensing element which senses differential pressure and provides a linear 4 to 20 mA or DC voltage output equal to the specified pressure range
  • This technology reduces warmup shift while also reducing the effect of package stress for increased long term stability. In addition, the unit contains a de-pluggable terminal block that can be removed for ease of installation
  • This unit must be ordered with a single uni or bi-directional pressure range and output signal from +/- 0.1” of water column to a maximum pressure of +/- 40” of water column depending on your application
  • All MLP2 Series pressure transmitters are calibrated using NIST Certified equipment
  • Optional 3 or 5 point NIST Certificates are available and must be specified when placing your order.
  • Applications
    • Building and Duct Static Pressure
    • Filter Monitoring
    • Air Flow Measurement
    • Process Control
    • Roof Top Units
    • Air Handlers
    • Clean Rooms
    • Isolation Rooms
    • Data Centers

Differential Pressure, Panel Mount, 0.25 inWC

Full-Scale Output (FSO)

ModelDescription
A/MLP2-D25-W-B-A-A-0PBiDirectional, +/- 0.5% FSO, 4-20mA
A/MLP2-D25-W-B-A-B-0PBiDirectional, +/- 0.5% FSO, 0-5VDC
A/MLP2-D25-W-B-A-C-0PBiDirectional, +/- 0.5% FSO, 0-10VDC
A/MLP2-D25-W-B-B-A-0PBiDirectional, +/- 0.25% FSO, 4-20mA
A/MLP2-D25-W-B-B-C-0PBiDirectional, +/- 0.25% FSO, 0-10VDC
A/MLP2-D25-W-U-A-A-0PUniDirectional, +/- 0.5% FSO, 4-20mA
A/MLP2-D25-W-U-A-B-0PUniDirectional, +/- 0.5% FSO, 0-5VDC
A/MLP2-D25-W-U-A-C-0PUniDirectional, +/- 0.5% FSO, 0-10VDC
A/MLP2-D25-W-U-B-A-0PUniDirectional, +/- 0.25% FSO, 4-20mA
A/MLP2-D25-W-U-B-C-0PUniDirectional, +/- 0.25% FSO, 0-10VDC