Questions? Contact Us Now +1 (303) 772-6100

Automation &
Monitoring Solutions.

A/SCTV2 Split-Core 10 Vdc Output Analog Current Sensors by ACI

Manufacturer: ACI
SKU: A/SCTV2
*
$65.90
Availability: 0 in stock
Minimum Order Quantity is 1
Products specifications
Attribute nameAttribute value
Input Rating (A)10, 20, 50, 100, 150, 200, 250
Output10 Vdc
Shape/StyleSplit-Core
Supply VoltageInduced from the Monitored Conductor (Insulated Conductors only)
Error %1, 2
Opening (greatest dim.)0.75 in (19 mm)
# of Inputs1
SeriesSCTV2

Description

The ACT CTV2 Solid Core & SCTV2 Split Core 10 Vdc Voltage Output Analog Current Sensors are designed for use in any AC current monitoring application in which you are looking to monitor a particular piece of equipment for proper operation

  • All voltage output current sensors use an “Average” current measuring method and should be used in applications where a pure Sinusoidal AC waveform that has very little or no distortion/noise on the conductor being monitored
  • Applications may include monitoring a resistive type load such as an incandescent light bulb or heating element as well as any single
    speed linear load
  • Voltage Output current sensors are available in both solid and split-core versions which also includes a Patented 35 mm Din Rail mounting foot for easy installation in panel mount applications
  • The solid-core versions are a great choice for new installations or OEM applications in which cost sensitivity, lower trip points and environmental issues like dust and moisture may be of concern
  • The split-core version of the current sensors work great in retrofit applications and for use on service technicians vehicles since one or two parts will work in most applications and can be easily installed without disconnecting any wires
  • For best results, the voltage output current sensors should not be used in applications with switching power supplies or variable speed drives due to the limited operating frequency range
  • In applications where variable speed drives or waveforms include distortion/noise, ACI recommends the use of the A/CTA2-RMS or A/SCTA2-RMS Series sensors where you need to supply 24 VDC power to the current sensors with a 4-20 mA signal
  • A 249 Ohm or 499 Ohm 1 Watt resistor can be used to convert the 4-20 mA signal into a useable 1-5 or 2-10 VDC output signal at your building management system or PLC
  • Applications
    • Load Trending
    • Single Speed Loads
    • Pumps
    • Compressors
    • Fans
    • Preventative Maintenance
    • LEED
    • Project Justification (Calculating ROI)
    • Process Control
Part NumberSelectable Ranges
A/SCTV2-500 to 10/20/50A
A/SCTV2-1500 to 50/100/150A
A/SCTV2-2500 to 100/200/250A

Cross References:
Red Lion
CTL0501F
CTL2001F
Veris
H623-10
H623-20
H723LC
H923
H723HC