Products specifications
Attribute name | Attribute value |
---|
Input | 115/66 Vac, 230/132 Vac, 400/230 Vac, Supply voltage = Measuring voltage |
Supply Voltage | 115 Vac, 230 Vac, 400 Vac |
Functionality | Phase Asymmetry, Phase Failure, Phase Sequence |
Phase | 3P4W |
Contact | DPDT, 2CO |
Display | LED |
LED | Green, Yellow |
# of Inputs | 3 |
Series | Gamma |
Description
Tele Haase G2PF series monitors phase sequence, phase failure and detection of return voltage (by means of evaluating the asymmetry) in 3-phase mains
- Monitoring of phase sequence and phase failure
- Detection of reverse voltage
- Connection of neutral wire optional
- Supply voltage = measuring voltage
- DPDT / 2 change-over contacts
- Width 22.5mm
- Industrial design
- Time ranges
- Start-up suppression time: fixed, max. 500ms
- Tripping delay: fixed, max. 350ms
- Indicators
- Green LED ON: indication of supply voltage
- Yellow LED ON/OFF: indication of relay output
- Input circuit
- Supply voltage
- G2PF115VS02: 3(N)~115/66V terminals (N)-L1-L2-L3 (= measuring voltage)
- G2PF230VS02: 3(N)~230/132V terminals (N)-L1-L2-L3 (= measuring voltage)
- G2PF400VS02: 3(N)~400/230V terminals (N)-L1-L2-L3 (= measuring voltage)
- Input circuit Tolerance
- G2PF115VS02: 3(N)~99 to 132V
- G2PF230VS02: 3(N)~198 to 264V
- G2PF400VS02: 3(N)~342 to 457V
- Rated frequency: 48 to 63Hz
- Rated consumption
- G2PF115VS02: 3VA
- G2PF230VS02: 6VA
- G2PF400VS02: 9VA
- Measuring circuit
- Measured variable
- G2PF115VS02: 3VA
- G2PF230VS02: 6VA
- G2PF400VS02: 9VA
- a.c. Sinus, 48 to 63Hz
- Input
- G2PF115VS02: 3(N)~115/66V terminals (N)-L1-L2-L3 (= supply voltage)
- G2PF230VS02: 3(N)~230/132V terminals (N)-L1-L2-L3 (= supply voltage)
- G2PF400VS02: 3(N)~400/230V terminals (N)-L1-L2-L3 (= supply voltage)
- : 3(N)~ 115/66V terminals (N)-L1-L2-L3 (= supply voltage)
- Overload capacity
- G2PF115VS02: 3(N)~132/76V
- G2PF230VS02: 3(N)~264/152V
- G2PF400VS02: 3(N)~457/264V
- Input resistance
- G2PF115VS02: 5kΩ
- G2PF230VS02: 10kΩ
- G2PF400VS02: 15kΩ
- Rated surge voltage: 4kV