Products specifications
Attribute name | Attribute value |
---|
Input Rating (A) | 250, 400, 500, 800, 1000, 1500, 2000, 2500, 3000, 4000, 5000 |
Output | 4~20 mA |
Shape/Style | Flexible/Rope Coil |
Supply Voltage | 8~35 Vdc Loop Powered |
Error % | 1 |
Opening (greatest dim.) | 4 in (102 mm) |
# of Inputs | 3 |
Series | MGS |
Description
Magnelab's MGS-1200 series is a three-phase Rogowski coil (rope CT) and Integrator, with a 4~20mA DC output
- Essentially, it is an integrator, AC current transducer or signal conditioner that is designed to convert the Rogowski coil input voltage to a DC output of 4 to 20 milliamperes (4-20mA)
- In order to function properly, the transducer has to use a DC loop power supply, which can operate from 8 to 35 volts DC
- The flexible CT device comes with integrated screw terminals which allow it to be easily and safely installed
- The accuracy is 1%
- The maximum voltage of the device on bare conductor is 600 V
- It is CE and RoHS compliant, as well as being UL recognized and it comes with a 10 year warranty
- Features
- Input from 250 to 5,000 Amps or custom (model dependant)
- True RMS measurement and ideal for distorted Waveforms
- Self-powered from 4~20mA Loop
- LEDs on each phase indicate when unit is connected to suitable power
- Three 12 inch long coils
- 8 feet of insulated leads as standard, from Rope CT to integrator
- 8 feet of output leads, which come in three sets of 600V twisted pairs for the three phase CT
Part Number | Input Amps |
MGS-1200-250 | 250 |
MGS-1200-400 | 400 |
MGS-1200-500 | 500 |
MGS-1200-800 | 800 |
MGS-1200-1000 | 1000 |
MGS-1200-1500 | 1500 |
MGS-1200-2000 | 2000 |
MGS-1200-2500 | 2500 |
MGS-1200-3000 | 3000 |
MGS-1200-4000 | 4000 |
MGS-1200-5000 | 5000 |