Attribute name | Attribute value |
---|
Functionality | Star-Delta Start-Up |
Supply Voltage | 12~240 Vac, 12~240 Vdc |
Input Rating (V) | 12~240 Vac, 12~240 Vdc |
Contact | 2NO |
Output | 250 Vac |
Display | LED |
LED | Green, Yellow |
Series | Veo |
Description
Tele Haase V2ZS20 12-240V AC/DC Star-Delta start-up Relay has 4 Start Up Time Ranges, DPDT/2CO contact and Wide input voltage range
- Star-Delta start-up (S)
When the supply voltage U is applied, the star-contact switches into onposition (yellow LED illuminated) and the set star-time t1 begins (green LED flashing) - After the interval t1 has expired (green LED illuminated) the star-contact switches into off-position (yellow LED not illuminated) and the set transit-time
t2 begins - After the interval t2 has expired the delta-contact switches into on-position
- To restart the function the supply voltage must be interrupted and re-applied