Products specifications
| Attribute name | Attribute value |
|---|
| Input | 120 Vac, 230 Vac, 277 Vac, 347 Vac, 400 Vac, 600 Vac, 800 Vac, 208~240 Vac |
| CT Input | 333mV |
| Phase | 1P2W, 1P3W, 3P3W, 3P4W |
| Accuracy Class | 0.5 |
| Functionality | Current, Demand, Energy, Frequency, Power, Voltage |
| Communication | BACnet MS/TP, RS485 |
| Datalogging | No |
| Supply Voltage | Line |
| # of Inputs | 4 |
| Series | WattNode |
Description
WattNode® BACnet Standard and Revenue Model Bidirectional Networked Energy Meter
- The WattNode BACnet is a bidirectional networked energy meter offering energy measurement parameters such as energy (kW), power (kWh), voltage, current, demand, kVAR, kVARh, power factor, line frequency, etc
- These energy values are communicated using the BACnet communication protocol over RS-485 as individual phase measurements and sum or average readings
- The WattNode BACnet can be assigned MAC addresses from 0 to 63 using front panel DIP switches. Up to 64 WattNode BACnet meters can be daisy-chained on one RS-485 subnet
- The BACnet - (Building Automation Control Network) term is commonly used to refer to the ANSI/ASHRAE Standard 135, adopted and supported by the American Society of Heating, Refrigeration, and Air-Conditioning Engineers (ASHRAE)
- The BACnet protocol provides auto-discovery which is used for device and object discovery over the network
- The WattNode BACnet meter has been independently tested by the BACnet Testing Laboratories (BTL), and is BACnet certified
- The WattNode BACnet is available in standard and revenue-grade accuracy and can be used with any low voltage CT (0.333 Vac output)
- Revenue-grade system accuracy requires current transformers with class 0.6 or better accuracy
- The ACTL series of current transformers is available with Class 0.6 or Class 0.3 accuracy; these CTs are ideal for revenue-grade use for billing purposes, SREC and state revenue-grade requirements
- Certificates of calibration are available for the WattNode Revenue meters and the ACTL revenue-grade current transformers
- The WattNode BACnet’s compact size permits installation inside most electrical service panels, junction boxes and OEM equipment
- The WattNode BACnet is line-powered, therefore does not require a separate power source
- Diagnostic LEDs help ensure fast and correct installation as well as network communication
- The WattNode BACnet family of energy meters measure 1, 2, 3 phases in 2, 3, or 4 wire configurations, 120 to 600 Vac, 50 to 60 Hz
- Socomec offers a complete line of low-voltage, solid and split-core current transformers for 5 to 6000 amp loads
| Standard Model | Revenue Model | Description |
| WNC-3Y-208-BN | RWNC-3Y-208-BN | Single-Phase 120V with required neutral Single-Phase 3-Wire 120/240V 3-Phase 4-Wire Wye 120/208V |
| WNC-3Y-400-BN | RWNC-3Y-400-BN | Single-Phase 230V with required neutral 3-Phase 4-Wire Wye 230/400V |
| WNC-3Y-480-BN | RWNC-3Y-480-BN | Single-Phase 277V with required neutral 3-Phase 4-Wire Wye 277/480V |
| WNC-3Y-600-BN | RWNC-3Y-600-BN | Single-Phase 347V with required neutral 3-Phase 4-Wire Wye 347/600V |
| WNC-3D-240-BN | RWNC-3D-240-BN | Single-Phase 208V (No neutral) Single-Phase 240V (No neutral) Single-Phase 3-Wire 120/240V 3-Phase 3-Wire Delta 208V–240V (No neutral) 3-Phase 4-Wire Wye 120/208V |
| WNC-3D-400-BN | RWNC-3D-400-BN | 3-Phase 3-Wire Delta 400V (No neutral) 3-Phase 4-Wire Wye 230/400V |
| WNC-3D-480-BN | RWNC-3D-480-BN | 3-Phase 3-Wire Delta 480V (No neutral) 3-Phase 4-Wire Wye 277/480V |