Products specifications
| Attribute name | Attribute value |
|---|
| Input | 120 Vac, 230 Vac, 277 Vac, 347 Vac, 400 Vac, 480 Vac, 600 Vac, 800 Vac, 208~240 Vac |
| CT Input | 333mV |
| Phase | 1P2W, 1P3W, 3P3W, 3P4W |
| Accuracy Class | 0.5 |
| Functionality | Current, Demand, Energy, Frequency, Power, Voltage |
| Communication | Lonworks |
| Datalogging | No, Yes |
| Supply Voltage | Line |
| # of Inputs | 4 |
| Series | WattNode |
Description
WattNode® for Lonworks® Models Bidirectional Networked Energy Meter and WattNode® Logger
- The WattNode for LonWorks is a networked energy meter that measures both energy consumed and energy produced (bidirectional)
- It provides electrical measurements such as energy (kWh), power (kW), voltage, current, kW demand, kVAR, kVARh, power factor, line frequency, etc
- These measurement values are communicated using the LonTalk® communication protocol as individual phase measurements and sum or average readings
- Measurements are transmitted as Standard Network Variable Types (SNVTs) through a LonWorks gateway
- LonWorks is a networking platform developed by Echelon Corporation that supports interconnection of various devices through a twisted pair connection
- The communication protocol (LonTalk) is an accepted standard for control networking (ANSI/CEA-709.1-B)
- The WattNode for LonWorks meter is available in standard and revenue-grade accuracy and can be used with any low voltage (0.333 Vac) output CT
- Revenue-grade accuracy requires the use of current transformers with class 0.6 or better accuracy
- The ACTL series of current transformers are available with class 0.6 or class 0.3 accuracy; these CTs are ideal for revenue grade applications such as tenant billing, Solar Renewable Energy Credit (SREC), and utility revenue-grade requirements
- Calibration certificates are available for the WattNode Revenue meters and the ACTL revenue-grade current transformers
- The WattNode meter’s compact size permits installation inside most electrical service panels, junction boxes, and OEM equipment
- The WattNode LonWorks meter is line-powered and does not require a separate power source
- The complete line of WattNode energy meters measure 1, 2, or 3 phases in 2, 3, or 4 wire configurations, 120 to 600 Vac, 50 to 60 Hz
- Socomec offers a complete line of low-voltage, split-core and solid-core current transformers with ratings from 5 to 6000 amps
| Standard Model | Logger Model | Revenue Model | Description |
| WNC-3Y-208-FT10 | WNC-3Y-208-FT10-L | RWNC-3Y-208-FT10 | Single-Phase 120V with neutral Single-Phase 3-Wire 120/240V 3-Phase 4-Wire Wye 120/208V |
| WNC-3Y-400-FT10 | WNC-3Y-400-FT10-L | RWNC-3Y-400-FT10 | Single-Phase 230V with neutral 3-Phase 4-Wire Wye 230/400V |
| WNC-3Y-480-FT10 | WNC-3Y-480-FT10-L | RWNC-3Y-480-FT10 | Single-Phase 277V with neutral 3-Phase 4-Wire Wye 277/480V |
| WNC-3Y-600-FT10 | WNC-3Y-600-FT10-L | RWNC-3Y-600-FT10 | Single-Phase 347V with neutral 3-Phase 4-Wire Wye 347/600V |
| WNC-3D-240-FT10 | WNC-3D-240-FT10-L | RWNC-3D-240-FT10 | Single-Phase 208V (No neutral) Single-Phase 240V (No neutral) Single-Phase 3-Wire 120/240V 3-Phase 3-Wire Delta 208V–240V (No neutral) 3-Phase 4-Wire Wye 120/208V |
| WNC-3D-400-FT10 | WNC-3D-400-FT10-L | RWNC-3D-400-FT10 | 3-Phase 3-Wire Delta 400V (No neutral) 3-Phase 4-Wire Wye 230/400V |
| WNC-3D-480-FT10 | WNC-3D-480-FT10-L | RWNC-3D-480-FT10 | 3-Phase 3-Wire Delta 480V (No neutral) 3-Phase 4-Wire Wye 277/480V |