Products specifications
Attribute name | Attribute value |
---|
Input Rating (A) | 5, 50 |
Output | 0.333 Vac |
Shape/Style | Split-Core |
Error % | 0.5 |
Opening (greatest dim.) | 0.5 in (13 mm) |
# of Inputs | 1 |
Series | LN2 |
Description
Sentran Model LN2 is an indoor type CT with full scale input range selection up to 100A
- An internal voltage setting resistor sets the full-scale output voltage
- This resistor also serves as open circuit shock protection for the installer
- The LN2 Split Core current transformer has been used to measure and record short duration fault currents up to 120A or more when installing over the 5A output lead of a standard instrument current transformer
- Customers using multiple input fault recorders find the LN2 very adaptable and accurate
- Specifications
- Input Current: AC current, 50/60Hz sinewave
- Over-Current: Designed for short duration fault currents (typically 120% < 5 seconds)
- Voltage Rating: 600VAC insulated conductors
- Interface Impedance for AC Voltage Style: Minimum of 50k Ohm resistive
- Output Resistance: 100 Ohms or less -- depends on input range for up to 1Vac output
- Ratio/Linearity Accuracy: At full scale, +/-0.5% or better
- Phase Displacement or Shift: 30' maximum @ 60Hz
- Phase Connection Relationship: White wire positive arrow towards input source
- Bandwidth: 50Hz to 60Hz (Contact Aim Dynamics for wideband applications)
Part No. | Input Rating (A) | Output |
LN2-5A:333mV(0.5%) | 5 | 0.333 V |
LN2-50A:333mV(0.5%) | 50 | 0.333 V |
Cross References:
Optosolutions
OPTOEMU-ACT-0750-050