Products specifications
Attribute name | Attribute value |
---|
Input Rating (A) | 250 |
Output | 4~20 mA |
Shape/Style | Split-Core |
Supply Voltage | 20~30 Vdc Loop Powered |
Error % | 2 |
Opening (greatest dim.) | 0.9 in (24 mm) |
# of Inputs | 1 |
Series | MCT |
Description
The MCT-0024-250 Split Core Current Transformer has a 4-20 mA DC output with a 24 mm opening
- The MCT-0024-250 measures 250 Amp AC current
- This 4-20 mA Output CT is powered from the 4-20 mA DC loop circuit
- In most cases a loop voltage of 20 VDC is sufficient to power the device
- However, if you are using a shunt in the current loop to generate a detectable voltage (e.g. 250 Ohm), you must take the voltage drop across the shunt into account
- Of course you may also provide additional voltage to the 4-20 mA DC loop if necessary
- The MCT-0024-250 is ± 2% accurate at full scale
- Ripple within 2% of output voltage
- It has a response time of 100 ms
- 4-20 mA CTs are popular because they differentiate a fault condition from zero detection
- With the MCT-0024-250, when there is no current on the primary, the measuring device will still see a 4 mA signal
- Similarly, at the rated current, the measuring device will see 20 mA
- However, when the loop circuit is broken for any reason, as you’d expect, the measuring device will see 0 mA, and the unit detects an error condition
- Because of this special ability to detect error conditions, 4-20 mA Output CTs are often used in control applications (you wouldn’t want to something to be controlled erroneously if the circuit was broken!)
- The MCT-0024-250 can be easily used in retrofitting applications because the split core current transformer opens and closes easily
Cross References:
Veris
H721LC
H721HC
Red Lion
CTL0052S
CTL0502S
CTR05000