Products specifications
Attribute name | Attribute value |
---|
Input Rating (A) | 5, 10, 20, 50, 100 |
Output | 4~20 mA |
Shape/Style | Split-Core |
Supply Voltage | 20~30 Vdc Loop Powered |
Error % | 2 |
Opening (greatest dim.) | 0.6 in (16 mm) |
# of Inputs | 1 |
Series | MCT |
Description
The MCT-0016 Split Core Current Transformer series have a 4~20mA DC (4-20mA) output with a 16 mm opening
- The MCT series measure AC current 5 Amps up to 100 Amps (model dependent)
- This 4~20mA Output CT is powered from the 4~20mA DC loop circuit
- In most cases a loop voltage of 20 Vdc is sufficient to power the device
- However, if you are using a shunt in the current loop to generate a detectable voltage (e.g. 250 Ohm), you must take the voltage drop across the shunt into account
- Of course you may also provide additional voltage to the 4~20mA DC loop if necessary
- The MCT-0016 is ± 2% accurate at full scale
- Ripple within 2% of output voltage
- It has a response time of 100 ms
- 4~20mA CTs are popular because they differentiate a fault condition from zero detection
- With the MCT-0016, when there is no current on the primary, the measuring device will still see a 4 mA signal
- Similarly, at the rated current, the measuring device will see 20 mA
- However, when the loop circuit is broken for any reason, as you’d expect, the measuring device will see 0 mA, and the unit detects an error condition
- Because of this special ability to detect error conditions, 4~20mA Output CTs are often used in control applications (you wouldn’t want to something to be controlled erroneously if the circuit was broken!)
- The MCT-0016 can be easily used in retrofitting applications because the split core current transformer opens and closes easily
Part Number | Input Amps |
MCT-0016-005 | 5 |
MCT-0016-010 | 10 |
MCT-0016-020 | 20 |
MCT-0016-050 | 50 |
MCT-0016-100 | 100 |